Professional Psychrometric Analysis Tool
Unit System
🌡️
Metric SI °C · kJ/kg · m³/s · kPa
🇺🇸
Imperial I-P °F · BTU/lb · CFM · psi
Language / Taal / Langue
💡 Quick Start Guide
⚙ Chart Settings
Temperature Axis (°C)
Humidity Ratio (g/kg)
Overlays
ASHRAE 55 comfort zone
State Point
Dry Bulb
Wet Bulb
Rel. Humidity
Hum. Ratio
Enthalpy
Dew Point
Hover chart to read psychrometric properties
0 points 0 processes
About
What is a Psychrometric Chart?
The psychrometric chart is the fundamental design tool of HVAC engineering. It plots the thermodynamic properties of moist air — temperature, humidity, and energy — allowing engineers to visualise and calculate every air conditioning and ventilation process. PsychroFlow delivers altitude-corrected psychrometric calculations for HVAC engineers worldwide, with a process-driven workflow built for professional practice.
📊
What it shows
Every point on the chart is a unique thermodynamic state of air. The horizontal axis is dry bulb temperature. The vertical axis is humidity ratio. The curved boundary on the left is the saturation curve (100% relative humidity).
🏠
Why it matters
Every HVAC design decision — coil sizing, AHU selection, humidifier capacity, duct conditions — starts with the psychrometric chart. It is the language of air conditioning engineering, used from preliminary design through to commissioning.
🇪🇦
Altitude correction
Elevation significantly affects all psychrometric calculations. PsychroFlow corrects atmospheric pressure using the ICAO standard atmosphere formula, ensuring accurate results for any location worldwide.
📚
Standards basis
All calculations use the ASHRAE Handbook of Fundamentals — the same standard used in HAP, IDA ICE, and all professional HVAC software. Applicable under SANS 10400-O and ASHRAE 62.1.
The Eight Air Properties
Tdb
Dry Bulb Temperature
°C (or °F)
The ordinary temperature measured by a thermometer. The horizontal axis of the chart.
Twb
Wet Bulb Temperature
°C
Temperature of adiabatic saturation. Lines slope diagonally down-right across the chart.
Tdew
Dew Point
°C
Temperature at which air saturates when cooled at constant pressure. Critical for condensation control.
RH
Relative Humidity
%
Ratio of actual vapour pressure to saturation pressure. Shown as curved lines on the chart.
W
Humidity Ratio
g/kgda
Mass of water vapour per kg of dry air. The vertical axis. Also called moisture content.
h
Specific Enthalpy
kJ/kgda
Total heat content per kg of dry air. h = 1.006T + W(2501 + 1.86T). Used for all energy calculations.
v
Specific Volume
m³/kgda
Volume per kg of dry air. Used to convert volumetric to mass flow rate. Increases with temperature.
Pv
Vapour Pressure
kPa
Partial pressure of water vapour in the moist air mixture. Used in humidity ratio calculations.
HVAC Processes Explained
❄️
Cooling & Dehumidification
When air passes over a cooling coil below its dew point, both temperature and humidity drop. The process line moves toward the lower-left, touching the saturation curve at the Apparatus Dew Point (ADP). The bypass factor tells you how much air misses the coil surface.
🔥
Sensible Heating
Air temperature rises with no change in humidity ratio (W stays constant). The process line moves horizontally to the right. Used for heating coils, reheat coils in hospitals and laboratories, and heat pumps in heating mode.
💧
Humidification
Steam humidification (isothermal) moves vertically upward at constant temperature. Adiabatic humidification follows the wet bulb line — temperature drops as humidity rises. Used in pharmaceutical cleanrooms, hospitals, and data centres.
🌊
Evaporative Cooling
Water evaporates into the airstream at approximately constant enthalpy, following the wet bulb temperature line. Temperature decreases while humidity increases. Most effective in dry, hot climates. Widely used in direct and indirect evaporative coolers.
Heat Exchanger (HRV/ERV)
A heat exchanger transfers energy from warm exhaust air to cooler incoming supply air (or vice versa). The supply air state moves toward the exhaust air state by a fraction equal to the heat exchanger efficiency rating (typically 60–85%).
Return Air Mixing
Outside air (OA) and return air (RA) are mixed before the cooling or heating coil. The mixed air state falls on the straight line between the two states, at a position determined by the mass flow ratio. Reducing OA fraction reduces cooling load but compromises indoor air quality.
Engineering Reference

Psychrometric Theory for HVAC Engineers

The psychrometric chart is the fundamental analytical tool of mechanical HVAC engineering. It graphically represents the thermodynamic properties of moist air and every process that changes them — from cooling coil sizing and AHU design to cleanroom humidity control and energy recovery.

01 What the Psychrometric Chart Shows

Every point on the psychrometric chart represents a unique, fully defined thermodynamic state of moist air. The horizontal axis is dry bulb temperature (Tdb). The vertical axis is humidity ratio (W) — the mass of water vapour per kilogram of dry air. The curved boundary on the left is the saturation curve (100% RH), representing the maximum moisture the air can hold at each temperature. All real air states exist to the right and below this curve.

Overlaid on the chart are families of lines for constant relative humidity (curved), constant wet bulb temperature (diagonal), and constant specific enthalpy (nearly parallel to wet bulb lines). These lines allow any two known properties to uniquely locate the full air state.

02 Why Every HVAC Engineer Needs It

No HVAC design decision stands alone. Cooling coil selection, AHU sizing, chiller plant capacity, humidifier specification, heat recovery efficiency, duct insulation thresholds, and indoor air quality compliance — all are grounded in psychrometric analysis. The chart translates between the invisible physical properties of air and the engineering quantities that determine system performance and energy consumption.

In practice, psychrometric analysis determines the sensible and latent load split of a cooling or heating process, which directly drives equipment selection and energy modelling. A 10°C drop in dew point target can halve the latent load on a cooling coil — this is not visible without plotting the process.

03 The Eight Psychrometric Properties

Any two independent properties fully define the moist air state. PsychroFlow calculates all eight from any valid pair using ASHRAE Handbook of Fundamentals equations.

Tdb
Dry Bulb Temperature
°C (or °F)

The standard air temperature measured by a thermometer. Forms the horizontal axis of the chart. Used for sensible heat calculations: Qs = ṁ × cp × ΔTdb.

Twb
Wet Bulb Temperature
°C

Temperature at adiabatic saturation. Diagonal lines slope down-right across the chart. Critical for cooling tower performance, evaporative cooler effectiveness, and coil selection.

Tdp
Dew Point Temperature
°C

Temperature at which air becomes saturated when cooled at constant pressure. Determines condensation risk on cold surfaces. Key for window glazing selection and cold pipe insulation design.

RH
Relative Humidity
%

Ratio of actual water vapour pressure to saturation pressure at the same temperature: RH = Pw/Pws × 100%. Shown as curved lines. Critical comfort and IAQ parameter — ASHRAE 55 targets 30–60%.

W
Humidity Ratio
g/kgda

Mass of water vapour per kg of dry air. Forms the vertical axis. Constant W means no moisture addition or removal (pure sensible process). W = 0.621945 × Pw/(P − Pw).

h
Specific Enthalpy
kJ/kgda

Total heat content per kg of dry air: h = 1.006T + W(2501 + 1.86T). Used for all coil duty calculations. Qtotal = ṁda × Δh. Does not equal sensible heat unless W is constant.

v
Specific Volume
m³/kgda

Volume of moist air per kg of dry air. Used to convert between volumetric flow (m³/s from fans) and mass flow (kg/s for energy calculations): ṁda = Qvol/v.

Pv
Vapour Pressure
kPa

Partial pressure of water vapour in the moist air mixture. Foundation of all humidity calculations. Saturation vapour pressure Pws(T) is computed via the Magnus formula. RH = Pv/Pws × 100%.

04 Apparatus Dew Point & Bypass Factor

When moist air is cooled below its dew point over a cooling coil, the process line extended to the saturation curve defines the Apparatus Dew Point (ADP) — the effective mean surface temperature of the coil. It is not the refrigerant temperature; it is the thermodynamic fingerprint of the coil performance.

The Bypass Factor (BF) quantifies the fraction of air that passes through the coil without making effective thermal contact with the coil surface:

BF = (Tleaving − ADP) ÷ (Tentering − ADP)

A BF of 0.05–0.15 indicates good coil design (multi-row, adequate fin density, low face velocity). A BF above 0.25 suggests poor coil contact — often caused by excessive face velocity (>2.5 m/s), too few rows, or wide fin spacing. The Contact Factor (CF = 1 − BF) represents the fraction of air fully conditioned to the ADP.

05 Sensible Heat Ratio (SHR)

The Sensible Heat Ratio describes the proportion of total cooling or heating that changes the air temperature (sensible) versus the proportion that changes the moisture content (latent):

SHR = Qsensible ÷ Qtotal = (ṁ × cp × ΔT) ÷ (ṁ × Δh)

SHR is graphically the slope of the process line on the psychrometric chart. A horizontal line (SHR = 1.0) is pure sensible heating or cooling. A steeper downward slope indicates significant dehumidification.

Design SHR targets vary by application: offices 0.85–0.95, hospitals 0.75–0.85, pharmaceutical cleanrooms 0.65–0.80, data centres near 1.0. Matching the supply air SHR to the space load SHR is fundamental to avoiding over- or under-dehumidification.

06 HVAC Processes on the Chart

❄️

Cooling & Dehumidification

Air crosses a cooling coil below its dew point. The process line moves toward the lower-left, ending on or near the saturation curve at the ADP. Dominant process in air conditioning design. Determines cooling coil UA, refrigerant capacity, and chiller plant sizing. Both sensible and latent loads must be met simultaneously.

🔥

Sensible Heating

Temperature rises at constant humidity ratio (W). Process line is horizontal. Used for heating coils, electric strip heaters, reheat coils in VAV terminal units, and heat pumps in heating mode. Relative humidity drops significantly during sensible heating — this drives winter humidification requirements.

💧

Humidification

Steam (isothermal): W increases at constant Tdb — vertical line on the chart. Adiabatic (evaporative): follows the wet bulb line, T drops while W rises. Steam humidification is used in critical environments (hospitals, laboratories, cleanrooms) where temperature control precision is essential. Sizing: ṁsteam = ṁda × ΔW.

🌬️

Evaporative Cooling

Near-constant enthalpy process along the wet bulb line. Temperature falls as humidity rises. Effectiveness = (Tdb,in − Tdb,out) / (Tdb,in − Twb,in). Most effective in hot, dry climates (effectiveness 70–90%). Widely used in data centres, industrial applications, and as pre-cooling for DX systems.

Heat Recovery (HRV / ERV)

A heat exchanger transfers enthalpy from exhaust air to supply air (or vice versa). HRV (sensible only) moves state along a line toward the exhaust condition. ERV (enthalpy exchanger) transfers both sensible and latent energy. Efficiency = (hout − hin) / (hexhaust − hin). Critical for energy-efficient ventilation in ASHRAE 90.1 compliance.

Return Air Mixing

Outside air (OA) and return air (RA) are mixed upstream of the conditioning coil. The mixed air state lies on the straight line between OA and RA states, at a position set by the mass flow ratio. Reducing OA fraction saves cooling energy but reduces IAQ. Minimum OA is governed by ASHRAE 62.1 or local equivalent. PsychroFlow calculates the mixed air state for any OA fraction.

07 Altitude and Atmospheric Pressure Correction

Atmospheric pressure decreases with elevation following the ICAO standard atmosphere model. This is not a minor correction — at 1750 m elevation, atmospheric pressure is approximately 82 kPa versus 101.3 kPa at sea level, an 18.5% reduction. Since humidity ratio W is directly proportional to vapour pressure and inversely proportional to atmospheric pressure, a given relative humidity corresponds to a significantly lower W at altitude.

PsychroFlow applies the ICAO standard atmosphere formula for all calculations:

P = 101.325 × (1 − 2.2558 × 10⁻⁵ × z)⁵·²⁵⁵⁸ kPa

where z is elevation in metres. This matches the formula used in ASHRAE Handbook of Fundamentals and major simulation tools (HAP, IDA ICE, EnergyPlus).

The practical consequences of altitude for HVAC design are significant:

  • Fan power increases because volumetric flow must increase to deliver the same mass flow rate at reduced density
  • Cooling coil capacity reduces because the same volumetric airflow carries less mass — coil selection at sea-level conditions will be undersized
  • Evaporative cooling effectiveness improves because the wet bulb depression is larger at altitude
  • Refrigerant pipe sizing must account for reduced suction pressure ratio
  • AHU filter pressure drops require correction when specifying at altitude

08 Key ASHRAE Standards for Psychrometric Design

ASHRAE 55
Thermal Environmental Conditions for Human Occupancy

Defines the acceptable temperature and humidity ranges for human comfort. The comfort zone on a psychrometric chart typically falls between 20–26°C dry bulb and 30–60% RH. Operative temperature, clothing insulation (clo), and metabolic rate are additional variables. PsychroFlow can overlay the ASHRAE 55 comfort zone on the chart.

ASHRAE 62.1
Ventilation and Indoor Air Quality

Sets minimum outdoor air ventilation rates and indoor air quality requirements for non-residential buildings. Directly impacts the OA/RA mixing ratio, which is a core PsychroFlow process type. Moisture-related IAQ requirements (prevention of mould at surfaces <70% RH) are determined through dew point analysis.

ASHRAE 90.1
Energy Standard for Buildings

Specifies minimum energy efficiency requirements including heat recovery, economiser cycles, and humidity control. The psychrometric chart is the primary tool for demonstrating compliance with economiser operation limits and energy recovery calculations.

ASHRAE Fundamentals Ch.1
Psychrometrics — The Calculation Basis

PsychroFlow implements the equations in ASHRAE Handbook of Fundamentals Chapter 1 for all property calculations. Saturation pressure uses the Antoine/Magnus equation. Humidity ratio, enthalpy, specific volume, wet bulb, and dew point are all computed per ASHRAE 2017 HoF for metric SI units.

How to Use PsychroFlow
PsychroFlow uses a process-driven workflow. Set your site conditions and starting air state in the sidebar, then add processes one by one. Each process calculates the end state and plots it on the chart.
1
Set Site Conditions
Select your SA city from the sidebar dropdown (sets elevation and pressure automatically), or enter elevation manually. The atmospheric pressure updates in real time.
2
Enter Starting Air Conditions
Enter the starting dry bulb temperature and select a second known property (RH, wet bulb, humidity ratio, or dew point). Enter the system airflow. Click Set Starting Conditions to plot Point 0 on the chart.
3
Select a Process Type
Click one of the process buttons in the sidebar: ❄ Cooling, 🔥 Heating, 💧 Humidification, 🌊 Evaporative Cooling, ⇄ Heat Exchanger, ⊕ Return Air Mix, or ✏ Custom.
4
Enter End Conditions and Calculate
Enter the target leaving conditions or process parameters. Click Calculate. The process is drawn on the chart and results appear in the tables below the chart.
5
Add More Processes
Click + Add Process in the sidebar. The next process automatically starts from the end of the previous one. Example: cooling from 33°C to 13°C, then reheating from 13°C to 22°C. All processes show simultaneously on the chart.
6
Generate PDF Report
Click the Report tab. Enter project and engineer details. Click Generate PDF Report. A professional A4 report opens in a new window — use Print → Save as PDF.
Chart Controls
The floating toolbar at the bottom-left of the chart: opens chart settings (axis ranges, comfort zone). RH/WB/h toggle those line layers. + zooms in centred on the chart. resets to the default view (-15 to +40°C).
Hover your cursor near any plotted state point to see a full property tooltip. The status bar below the chart shows your cursor position in real time.
Keyboard Shortcuts
Ctrl+Z — Undo last process.   Ctrl+P — Open Report tab.
Generate Engineering Report
Enter project details below. The report includes the psychrometric chart, all state point properties, and process analysis.
Project Details
Engineer Details
Notes
Report opens in new window — Print → Save as PDF
Settings
Unit System
🌡️
Metric SI°C · kJ/kg
🇺🇸
Imperial I-P°F · BTU/lb
Chart Layers
Relative Humidity lines
Wet Bulb lines
Enthalpy lines
Grid lines
Session
Done